E-1.1, r. 1 - Regulation respecting energy conservation in new buildings

Full text
118. Power operated dampers prescribed in sections 115 to 117 must be designed so that air flow with the damper in the closed position does not exceed 50 L/s per square metre of cross sectional area at a gauge pressure of 250 Pa.
O.C. 89-83, s. 118.